GENERAL SAFETY AND WIRING PRECAUTIONS

Review the following safety precautions to avoid injury and prevent damage to the DE-4000 System or any devices connected to it.

● USE ONLY AS SPECIFIED To avoid potential hazards, install and use this system only as specified. Only qualified personnel should perform installation, wiring, and configuration procedures.

● CONNECT AND DISCONNECT PROPERLY Caution – Do not connect or disconnect equipment, connectors, plugs, etc., unless power has been verified to be off.

● PROPERLY GROUND THE SYSTEM The ground terminal on the Input Power connector of each module must be connected to panel ground, which should be the same as engine ground. DO NOT connect directly to common coil ground.

● SINGLE POINT SYSTEM GROUND The power supply minus (-) terminal and the ground (GND) terminal are common. GND must be connected to panel ground. Minus(-) must be connected to power supply minus. Common point is the panel ground which must be the same as engine ground.

● OBSERVE ALL TERMINAL RATINGS To avoid damage to the system and personnel, observe all ratings and markings on the modules. Consult the individual sections of this manual for further ratings information before making connections to the modules.

● MOUNTING/ENCLOSURE The DE-4000 System must be mounted in a suitable enclosure.

● POWER AND POWER DISCONNECT

  1. Power must be from a Class 2 power source with transient protection or from a 24-volt battery system.
  2. The power to the DE-4000 System must be installed in accordance with the requirements of the National Electrical Code (US) and the Canadian Electrical Code (Canada)
  3. Over-current power protection is required for the DE-4000 System.
  4. A separate disconnect for the DE-4000 System is required. An Altronic Power Management Module (PMM), a fuse block, or circuit breaker, must be used from the source power to the DE-4000 in the panel.
  5. The power disconnect must be marked as the over-current and disconnect for the DE-4000 System.

 

OVERVIEW

General

The DE-4000 is a Control and Safety Shutdown system specifically designed to protect, monitor and control critical rotating machinery such as engines or motor-driven compressors, pumps and generators operating in normal, harsh, and/or hazardous environments.

Description

The system uses state-of-the-art microcontrollers and has a multi-level software architecture. The Controller Module and Terminal Module run a real-time operating system to ensure that safety and control functions are reliable and deterministic. The Controller Module also contains a System-On-Module (SOM) that has an embedded web server and also a key-value datastore. The SOM module offloads the user interface functionality and also the Modbus communication to enable the Controller Module and Terminal Module to run real-time without being affected by connected clients. The system is fully scalable/expandable, allowing users to incorporate a single control system technology across a wide range of applications — low, medium, and high-spec.

WARNING: Deviation from these instructions may lead to improper engine operation which could cause personal injury to operators or other nearby personnel.

 

 

 I/O

The base DE-4000 configuration offers 32 inputs that can be individually configured for use with switch contacts, thermocouples or analog transducers. The base system also contains 12 digital and 4 analog (4-20mA) outputs. A maximized DE-4000 system provides 160 configurable inputs, 44 digital and 20 analog outputs.

 

Hardware Safety

The Hardware Safety Connection (HSC) is available as a backup safety shutdown channel to the communications shutdown. The HSC connects the Terminal Modules to the Controller Module. It is independent hardware that is used as an independent shutdown signal from any of the terminal modules. When activated it triggers Discrete Output #1 (typically used as the fuel shutdown) on the Controller Module, independent of the Controller Module’s microcontroller.

WARNING: The control and safety shutdown system must be configured prior to use on the machine. Reference the configuration manual DE-4000 OCM for instructions describing how to configure the controller for the specific application. Verify the configuration prior to commissioning the machine.

 

 

Web Interface

The system is Ethernet-based, including on-board web pages for system configuration (eliminating the need for a separate terminal program), operation, control applications, and remote monitoring. The intuitive system configuration web page operates on a “fill-in-the-blanks” basis whereby the application is not programmed, but configured. The operator selects the appropriate operating parameters and setpoints for each input channel, defines the operation of the digital and analog control outputs, configures the service meters, and establishes the frequency of system datalog sampling and recording.

 

HMI

A Human Machine Interface (HMI) Display Module is the user interface. The system being Ethernet-based allows for several Ethernet-based electronic devices to monitor and display information simultaneously. System data can simultaneously be displayed on a panel-mounted HMI, a laptop, a handheld display such as a mobile phone or tablet, as well as remotely.

 

Config Files

System Configuration files can be created via a laptop or the HMI Display Module, saved and downloaded, as well as uploaded, to other DE-4000 Systems. This allows for configuration portability for users operating several similar systems.

 

Bootloader Files

The Bootloader and current system versions can be updated in the Settings menu by connecting a USB drive containing the new firmware to the Controller Board.

 

Data logs are taken at user-defined intervals and are a compilation of the analog values being monitored by the DE, plus unit speed, status, and complete information on the first fault that caused a system shutdown (identity, value, date, time). Data log information is stored on a removable microSD card. Data log information can be retrieved locally or remotely. An integral data analysis/ trending package that is included with the web interface can display and graph this data for inspection and analysis.

 

Hardware

The system has three main parts:

● HMI Display (Panel Mounted) (691766-1)

● Controller Module (691759-1)

● Terminal Module, 32 channel (691760-1)

These components are interconnected with CAT5e Ethernet cable assemblies terminated on both ends with an RJ45 connector.

● Ethernet Cable, CAT5 0.3m (12“) (693221-1)

● Ethernet Cable, CAT5 1.0m (39”) (693221-2)

● Ethernet Cable, CAT5 2.0m (79“) (693221-3)

 

Power Req.

System power requirement is 10-32VDC, 5 amps max.

 

Operating Temperature

Ambient temperature range:

Controller Module and Terminal Module: –40°C to +85°C (–40°F to +185°F)

HMI Display Module: –30°C to +80°C (–22°F to +176°F).

 

Certifications

The DE-4000 System is CSA- and UL-certified for use in Class I, Division 2, Groups C and D hazardous locations.

 

HMI DISPLAY MODULE (691766-1)

General

The HMI Display serves as the user interface for the DE-4000 System. It is a panel-mounted 8” (diagonal), 1024 x 768 XGA, anti-glare/anti-reflective, 4:3 ratio, TFT LCD with PCAP (capacitive-touch) screen and LED backlight. The front of the display is sealed to IP67 for tough outdoor environments. The display has a 1000nit max LED intensity with auto or manual backlight dimming.

 

Interface

The touchscreen HMI Display is web-based and serves as the “Interface” for configuring the system, as well as the on-sight user display. The HMI communicates with the Controller Module via a standard CAT5e Ethernet patch cable. The required Ethernet cable is terminated with an RJ45 connector on each end. Industrial Ethernet cable assemblies are available from Altronic reference part numbers 693221-x, “x” represents the length.

 

Ethernet

The Ethernet port on the HMI contains two LED indicators; yellow indicates Ethernet activity, green indicates that a communication “link” has been established.

 

Membrane Buttons

A 5-key front-mounted, sealed membrane keypad allows for standard, often used keys (STOP, RESET, START). The membrane keypad allows these common keys to be accessible regardless if the screen is viewable. The STOP, RESET, and START keys are hard-wired to the back of the Display Module. During installation, these keys are wired to the Controller Module. These connections, external to the communications cable, allow for reliable hardware connections independent of the Display Module operation. The remaining two keys are F1 and F2. These keys can be assigned to frequently used functions.

 

Communication

The HMI Display displays the DE-4000 System configuration and real-time status. No programming or configuration data is stored in the HMI Display. All of the data is communicated to and from—and stored in—non-volatile memory on the Controller Module. The Controller Module memory retains the current configuration during normal operation, after compressor shutdown and a system power-down.

 

Mount

Front panel dimensions are 9“ x 9”. Screw mounting dimensions are 6“ x 6”. The mounting hardware is 10-24 studs and nuts. The HMI Display is designed to be mounted into the current Altronic DE Annunciator cutout. This allows for compatibility and ease of mounting to previous Altronic systems without the need to enlarge the panel cutout. Please note, however, that, when retrofitting an older DE-xxxx System Panel Mounted Display Module with the DE-4000 HMI Display Module, an additional 2“ on each side of the original cutout is required.

 

Backlight

The backlight intensity on the HMI is auto-adjusted using a light sensor mounted on the front of the HMI.

 

Front Glass

The front glass is made from high quality, damage resistant Gorilla Glass. The Gorilla Glass enables the HMI front to be exceptionally tough and damage resistant.

 

Power Req.

Input Power requirement to the HMI is 10-32 VDC, 0.8 amp typ. 2 amp max.

 

Operating Temperature

Operating temperature range is -30°C to +80°C (-22°F to 176°F)

 

Future Use

The HMI also contains the following communication ports: RS485, CAN, USB Host, and USB OTG. These ports are not currently used on the DE-4000 System.

 

Additional Display Options

ACM-4000 (691810-1)

The current configuration of the DE-4000 HMI display uses an ethernet connection to transfer data to it. Which then uses that data, and a built in processor to host graphics and information on the display.

To utilize other displays such as monitors or larger HMI’s that accept HDMI, the Altronic Compute Module can take in the ethernet connection from the DE-4000 and allow any HDMI based display to be connected.

Installation is plug and play, documentation for the ACM-4000 can be found Here – ACM-4000 Documentation

 

CONTROLLER MODULE (691759-1)

General

The Controller Module is the hub of the system. It is the main controller interfacing with up to five Terminal Modules, the HMI Display Module, and other systems. The scalable and expandable nature of the DE-4000 allows it to be used on the simplest safety-shutdown-oriented applications, on mid-range applications with minimal or moderate auto-start or capacity control requirements, and on highly-complex units where a significant number of points must be monitored and functions controlled simultaneously. The Controller Module is designed to be rail mounted.

 

Ethernet

The system’s communication protocol is Ethernet. The Controller Module connects to the other modules via a standard CAT5e Ethernet patch cable. The required Ethernet cable is terminated with a RJ45 connector on each end. Industrial Ethernet Cable assemblies are available from Altronic reference part numbers 693221-x, “x” represents the length.

Available Ethernet ports are as follows:

● 5 – Ethernet ports reserved to connect up to 5 Terminal Modules

● 1 – Ethernet port reserved to connect to the HMI Display

● 1 – Ethernet port reserved to connect to an outside network

DISCRETE OUTPUTS

The Controller Module has four discrete outputs rated 52VDC, 1.2 amp max. The discrete outputs provide a means of using the DE-4000 controller to interface with other systems on the engine/motor and compressor. The discrete outputs are typically used for on/off control of on-engine processes. Typical applications are: Fuel Valve, Ignition Shutdown, Purge, and Crank Disconnect. The discrete outputs can be configured for either shelf state (normally-open) or failsafe (normally-closed) operation and have an LED indicator associated with them. If a discrete output is configured for failsafe (energized for run), the LED will be ON in the normal run condition and OFF for a fault condition. For outputs that are configured for shelf state, the LED will be OFF for normal run condition and turn ON for a fault condition. The four discrete outputs are optically isolated, bipolar solid-state switches which are isolated from power supply minus and engine ground. These outputs can be wired as high-side or low-side configurations. The Output Modules are in the open (de-energized) condition when the unit is not powered.

 

DISCRETE INPUTS

There are three discrete inputs; STOP, RESET, START. These inputs can be connected to the hardware keypad on the Altronic HMI Display Module. They also can be connected to panel-mounted dry contact switches.

 

STATE INDICATING LEDS

There are four state-indicating LEDs: RUN state (green), TIMERS ACTIVE state (yellow), ALARM state (orange), and STOP state (red).

 

RS485 PORTS

There are two RS485 serial ports. The RS485 1 port is used for Modbus slave data, and the RS485 2 port is used for Modbus master data.

 

CAN PORT

One CAN port is available and it is marked CANH, and CANL

 

USB PORTS

The USB connectors are not to be used in a hazardous area. Assure area is safe before connecting or disconnecting to the USB connectors.

 

INPUT POWER

Input power requirement is 10-32VDC, 0.8 amp typical, 2 amps max. Overcurrent protection is provided with an easy to replace 5 amp automotive blade fuse. The 12-24VDC power for the Controller Module is to be connected to the INPUT POWER terminals marked (PWR+) and (PWR−); GND is to be grounded to panel ground. A dual-color green/red diagnostic LED indicates the system power status. Green indicates that input power is within the systems operating voltage range. Red indicates that input power is out of the proper operating range. Off indicates no—or very low—power.

 

OPERATING TEMPERATURE

The Controller Module has an operating temperature range of -40°C to +85°C (-40°F to 185°F)

 

WiFi ANTENNA

Antenna cable connection

The WiFi antenna connector on the Controller Module is a 6.35 mm, 50 ohm, jack style, threaded SMA type RF connector.

Qualified antenna types

The Wi-FI radio on the DE-4000 is designed to operate with a dipole-type antenna having a maximum gain of 2.14 dBi. Antennas having a gain greater than 2.14 dBi are strictly prohibited for use with the Wi-Fi radio on the Controller. The required antenna impedance is 50 ohms. Any antenna that is of the same type and of equal or less directional gain as listed above can be used. To reduce potential radio interference to other users, the antenna type and its gain should be so chosen that the equivalent isotropically radiated power (e.i.r.p.) is not more than that permitted for successful communication. Using an antenna of a different type or gain more than 2.14 dBi is prohibited.

 

TERMINAL MODULE (691760-1)

General

The Terminal Module is the point of interface between the field sensor wiring and the DE-4000 control system. All sensors enter the system through the Terminal Module. Control outputs, both analog and digital, are driven from the Terminal Module. The heart of the Terminal Module is a 32-bit microcontroller. The operating system runs in real-time to ensure that safety and control functions are reliable and deterministic. The interface to the Control Module is via the Ethernet cable. A DE-4000 System can contain one, or up to five each, Terminal Modules.

Each Terminal Module has the following I/O:

● 32 – input channels (individually configurable for use as NO/NC discrete inputs, J or K thermocouple inputs, or as analog inputs (0-5V or 4-20mA)

● 2 – speed inputs (0-10KHz)

● 4 – analog outputs (4-20mA)

● 8 – high-side or low-side discrete outputs (45V, 2 amp max)

● 8 – 5V, 100mA supplie

TERMINAL MODULE I/O POINT IDENTIFICATION

Up to five Terminal Boards can be used in a DE-4000 System. The system uses a simple Terminal Module/Channel number assignment method that identifies the Terminal Module and I/O point.

Each Terminal Module is assigned a number from 1 to 5 via the Board ID switch. Inputs and Outputs for each Terminal Module follow the acronym for each channel shown on the Terminal Module label. The format is: Terminal Module Number, a colon, then the I/O point acronym.

Examples:

T2:IN7 = Terminal Module 2, Input 7

T1:AO2 = Terminal Module 1, Analog Output number 2

 

BOARD ID SWITCH

The Terminal Modules contain a rotary BOARD ID switch. The BOARD ID switch is used to identify each Terminal Module connected to the DE-4000 System. Since each Terminal Module operates identically to each other in the system, the Board ID switch is used to differentiate each Terminal Module from the others. Terminal Module 1 must be set to BOARD ID “1”. Terminal Module 2 must be set to BOARD ID “2”, etc. Terminal Modules must be assigned in numerical order starting at BOARD ID 1 to 5. Upon power-up the Controller Module sends out a signal to “look” to see how many Terminal Modules are connected to the system and that they each contain a unique ID. Once each terminal module is assigned a “T” number using the board ID switch, the assigned number can be written with a “Sharpie” marker on each Terminal Module for identification reference. A white box near the board ID switch is made available as shown below.

 

INPUT CHANNELS

Each input can individually be configured for use as NO/NC discrete inputs, J or K thermocouple inputs, or as analog inputs (0-5V or 4-20mA). Each input contains a corresponding 4-position channel switch that must be set accordingly for proper operation. Switches are turned ON by moving them to the “ON” position (toward the connectors). Please see below for proper switch settings. For reference, the black part of the switch indicates the “on” position. The analog switch setting is OFF, OFF, OFF, ON.

The input channels contain overvoltage protection that helps prevent damage from inadvertent field mis-wires. They also contain channel to channel isolation to prevent one mis-wired channel from affecting other channels.

For analog sensors that require a +5 volt source, the Terminal Module can supply up to eight +5V sources of current up to 100mA each.

Please refer to figure 8 for Terminal Module Input Sensor wiring diagrams

N/O and N/C DISCRETE INPUTS

The Terminal Board inputs can accept standard normally-open and normally-closed dry contacts. The wetting current for sensor detection is supplied internally by the Terminal Module.

● For a normally-open sensor input, turn on switches 1 & 2 (or turn on switch 2 and place a shunt jumper between INx+ and INx-), connect the wire from the sensor to the INx+ input. The other wire from the N/O sensor is grounded to cause a fault.

● For a normally-closed sensor input, connect one wire from the sensor to INx+, the other on INx-. The sensor is closed for normal operation and opens upon a fault

 

 J or K THERMOCOUPLE INPUTS

Each Terminal Module can accept industry-standard type J or K thermocouples on inputs 01–32. Automatic cold junction compensation and linearity correction are built-in. The units can be configured for °F, °C, or °K. Both high and low setpoints are associated with each channel. The system can read type J thermocouples between -76°F and +1382°F (-60°C and +750°C) and type K thermocouples between -76°F and +1472°F (-60°C and +800°C). For both J and K type thermocouples the red insulation color is (-), the other color is the (+).

 

 INPUTS – PRESSURE TRANSDUCERS

The pressure transducers, Altronic P/N 691201-x and P/N 691204-x, are packaged in a rugged sealed case with an NPT pressure port, a corrosion resistant media cavity, and a Packard Electric Metri-Pack connector. The ranges available are 0-100, 300, 500, 1000, 2000, and 5000 PSIG for the 691201-x series and 0-50,100, 300, 500 PSIA for the 691204-x series, all of which have an overload rating of 1.5 times full scale without damage. The three wires from the transducer are: +5 volt excitation, +0.5 to 4.5 volt output, and minus return. These three wires connect directly to the Terminal Module using cable assembly P/N 693008-x.

 

TEMPERATURE TRANSDUCER

Temperature transducers, Altronic P/N 691202-300/691203-300, 691212-450/691213-450, and 691212-232/691213-232 are packaged in a sealed, stainless steel housing with a 5/8”-18 UNF threaded body and a Packard Electric Metri-Pack connector. Temperature transducers 691203/202-300 have a temperature measurement range of +5 to 300°F. Temperature transducers 691212/213-450 have a temperature range of -40 to +450°F. During configuration, the 691202/203-300 transducers are selected as Deg1 Type, the 691212/213-450 transducers are selected by choosing Deg2 Type, and the 691212/213-232 transducers are selected by choosing Deg3 type. The three wires from the transducers are: +5 volt excitation, temperature output voltage, and minus return. These wires connect directly to the Terminal Module using cable assembly P/N 693008-x.

 

INPUTS – DIFFERENTIAL MEASUREMENTS

Differential pressures or temperatures may be measured by using two consecutive channels. The transducers used to measure differential values must be of the exact same type and range. The first channel of the pair displays the basic parameter it is monitoring and the second channel of the pair displays the numeric difference in engineering units of its value subtracted from the first channel’s value. Setpoints for each channel monitor the displayed value of that channel. The second channel setpoints monitor the differential value.

 

 4-20mA INPUTS

The Terminal Module can accept 4-20mA inputs by selecting the internally-connected 200-ohm resistor (via DIP switch #3), creating a termination voltage of 0.8 to 4.0 volts. For proper 4-20mA operation, the input requires either switches 1 & 3 to be on or switch 3 to be on with an external shunt jumper wire between the + and – terminals.

 

 +5V TRANSDUCER SUPPLY

For convenience there are eight total 5V supplies rated at 100mA each for the purpose of supplying 5 volts DC to transducers. The 5V supplies are protected from shorts and reverse connection. The 5V supply contains a unique low forward voltage transistor that allows the output to be a tighter tolerance and to survive shorts and field mis-wires.

 

SPEED INPUTS

Each Terminal Module contains two speed inputs. Each speed input can be configured independently from the other. Examples of monitored speed inputs are engine RPM and turbo speed RPM.

Typical speed signals can come from magnetic pickups or Hall effect pickups monitoring the engine flywheel or other rotating gears. The monitored gear can be of some ratio to the speed of interest (the speed configuration page is used to select a ratio of gear teeth to speed of interest). The frequency range of the speed input is 0 to 100KHz. Nominal input voltage levels are 5 to 24 volts. Each speed input is protected from mis-wires of up to 200 volts max.

The RPMx- terminals are common to DC-. Connect the speed input to the terminals marked RPMx+ and RPMx-. Altronic magnetic pickups or Hall effect pickups are typical sources for RPM measurement.

● MAGNETIC PICKUP — Connect the two wires from the 691118 series or similar magnetic pickup to the Module at terminals RPMx+ and RPMx- using cable assembly 693104 series.

● HALL EFFECT PICKUP — Connect the three wires from the 791050 series Hall effect pickup to the module at terminals RPMx+, RPMx-, and a +5 volt source using cable assembly 593050 series. Connect pickup cable wire B to a +5V supply, wire A to terminal RPMx+ (plus), and wire C to terminal RPMx- (minus). In addition, a 10,000-ohm pull-up resistor must be placed across the +5V supply to GT of the monitor. Refer to the wiring diagrams for hookup details.

 

ANALOG OUTPUTS

Each Terminal Module provides four 4-20mA analog outputs. The analog outputs can be used for interfacing to actuators, I/P Transducers, governors, and other control hardware. These 4-20mA outputs are typically used to implement control strategies. For further information on typical control strategies, refer to the DE-4000 Operation and Configuration Manual.

Connect terminal AOx+ terminal to the plus (+) input, and the AOx- terminal to the (-) input of the device being controlled.

 

DISCRETE OUTPUTS

Each Terminal Module provides eight discrete outputs. DO1 through DO8 are fault protected, ground isolated, solid state switches that turn on from DOx+ to DOx-. Each discrete output is rated at 60V, 2A max. They are solid state smart switches with diagnostics (over current, over temp protection) and can be wired for high- or low-side operation. Dual LED indicators, one for each output, green indicates the output is energized, red indicates a fault condition. If an overload occurs, the red LED will illuminate indicating a fault condition. When the fault condition is removed, the switch will return to its normal operating condition.

 

HARDWARE SAFETY CONNECTION

The Hardware Safety Connection on the Terminal Module, when connected to the Controller Module, acts as an independent shutdown signal from any terminal module to the Controller Module. The DE-4000 System relies heavily on Communications over Ethernet for proper operation. If communications are interrupted, the Hardware Safety Connection provides the system a parallel path for shutdown. The Hardware Safety Connection is a separate independent connection to activate output DS1 on the Control Module, typically the fuel valve shutdown. If there is an interruption in communication, and the Terminal Module determines that a shutdown needs to take place, the fuel valve output located on the Controller Module, DS1, will activate, removing fuel to the engine and thus shutting it down independent of the normal operation of the Controller Module.

 

RS485 PORT

The RS485 serial port on the Terminal Module is marked RS485 A, RS485B, and SHIELD and is unused at this time.

 

CAN PORT

The CAN port on the Terminal Module is marked CANH, and CANL, and SHIELD and is unused at this time.

 

INPUT POWER REQUIREMENT

Input power requirement is 10-32VDC, 0.8 amp typical, 2 amps max. Over-current protection is provided with an easy-to-replace 5 amp automotive blade fuse. The 12-24VDC power for the Controller Module is connected to the INPUT POWER terminals marked (PWR+) and (PWR−); GND is grounded to panel ground. A LED lights green when proper power is applied to the Terminal Module. A red power LED indicates that the applied supply voltage is out of tolerance.

 

OPERATING TEMPERATURE

The Terminal Module has an operating temperature range of -40°C to +85°C (-40°F to 185°F)

 

MOUNTING

General

When the DE-4000 System is installed in a Class I, Division 2 hazardous area, it must be mounted in a suitable enclosure.

NOTE: Avoid mounting the HMI Display Module with the LCD display facing direct sunlight.
The display operating temperature range is -30C to +80C(-22F to -176F)

 

 

HMI DISPLAY MODULE

The HMI Display Module is designed to be mounted on the front insert of the Control Panel. In retrofit applications, the HMI Display Module can be inserted in the current Altronic DE Annunciator cutout without modifications. This allows for compatibility and ease of mounting in place of previous Altronic systems without the need to enlarge the panel cutout. Please note, however, that, when retrofitting an older DE-xxxx System panel-mounted Display Module with the DE-4000 HMI Display Module, an additional 2“ on each side of the original cutout is required. Front panel dimensions are 9” x 9“. Screw mounting dimensions are 6” x 6“. The mounting hardware is M5 x 0.8 threads. Mount the Display Module inside a control panel or to a suitable flat surface so that the display is at a convenient viewing height. A drilling template and mounting dimensions are provided.

 

CONTROLLER MODULE

Mount the Controller Module on the inner panel plate or to the side of the main panel. The Controller Module is designed to be rail-mounted onto commercially available 32 or 35mm DIN mounting rails. Two end brackets, P/N 604199, should be used to keep the module from sliding off the ends of the mounting rail. Controller Module dimensions are 10” x 5“ x 2.37”.

 

TERMINAL MODULE

Mount the Terminal Module on the inner panel plate or to the side of the main panel. The Terminal Module is designed to be rail-mounted onto commercially available 32 or 35mm DIN mounting rails. Two end brackets, P/N 604199, should be used to keep the module from sliding off the ends of the mounting rail. Terminal Module dimensions are 10“ x 5” x 2.37“. Terminal Modules can be mounted in a separate enclosure as long as the enclosure meets the requirements of the area.

 

PRESSURE TRANSDUCER

Mount the pressure transducer in the panel or in a manifold or tube off of the engine. Do not expose the pressure transducer to temperatures above 221°F (105°C).

IMPORTANT: Pressure Transducers will withstand overloads as high as 1.5 times rated pressure. If the overload rating is exceeded, failure may occur. Pressure fluctuations occur in most reciprocating systems; pick the transducer with a rating high enough to prevent overload by peak pressures of pulsations. It is recommended that a pressure snubber be used which will reduce the peak pressure applied to the transducer. The life of the transducer will be extended with the use of a snubber or pulsation dampener.

 

 

TEMPERATURE TRANSDUCER

 

Mount the temperature transducer in a thermowell on the engine or machine. The actual sensor is located at the bottom of the transducer body. To ensure accuracy, the tip of the probe should be surrounded by the measured media.

IMPORTANT: Do not exceed the absolute maximum rating of the transducers, 350°F(176°C) for the 691202/203-300 or 450°F(232°C) for the 691212/213-450. Care should be taken to protect the wiring and connectors from contact with hot surfaces.

 

 

WiFi ANTENNA

WiFi ANTENNA Mount the WiFi antenna outside of the enclosure. Attach the coax cable to the SMA connector.

 

WIRING

SYSTEM MODULE CONNECTIONS

The Controller Module is the hub of the system. Ethernet cables connect the Controller Module to the other modules via standard industrial-type CAT5e Ethernet patch cables. The required Ethernet cable is terminated with a RJ45 connector on each end. Industrial Ethernet Cable assemblies are available from Altronic, reference part numbers 693221-x, “x” represents the length. Ethernet Cable assemblies, terminated both end with RJ45 jacks.
● 693221-1 Ethernet Cable, CAT5 0.3m (12”)
● 693221-2 Ethernet Cable, CAT5 1.0m (39“)
● 693221-3 Ethernet Cable, CAT5 2m (79”)
Available Ethernet ports are as follows:
● 5 – Ethernet ports reserved to connect to up to 5 Terminal Modules
● 1 – Ethernet port reserved to connect to the HMI Display
● 1 – Ethernet port reserved to connect to an outside network

 

TERMINAL BLOCK WIRING

Pluggable Connectors with push-in spring-cage (PIT) connections are used for the input/output wiring on each module. The terminating wire, or wire with ferrule, can be inserted into the connector without the need of a tool. Fine gauge wire can also be used without a ferrule but will require using the push-in opening lever on the connector. To remove the wire, use a tool and press the opening lever “in” to release the wire.

NOTE: The signal connectors accept solid or fine-stranded wire (with ferrule) in the range of 24 to 16 AWG. Recommended strip length of the remaining bare wire is 9mm (.35″). A ferrule with a nominal length of 12mm (0.47″) is recommended. Each connector point contains a built-in test point of 1mm (.04″) diameter or 1.2 mm (.047″) diameter for troubleshooting purposes.

 

 

POWER WIRING

The DE-4000 System uses distributed wiring. Each module has its own power input terminals. Using a fuse block in series with the source power, connect the wires to the 10-32VDC INPUT POWER terminals on each module, positive to terminal (PWR+) and negative to terminal (PWR-); system power requirement is nominal 12 to 24VDC (5 amps max.). The GND terminal must be connected to panel ground which should be the same as engine ground. PWR- and GND are internally tied.

Normally-open sensors most often use the engine ground as the minus return path. For normally-open sensors to operate properly, engine ground, panel ground, and power supply minus MUST be at the same potential as PWR- and GND wires on the Terminal Module.

DO NOT ground this device directly to the ignition system common coil ground.

NOTE: The power pluggable connector accepts wire in the range of 24 to 12 AWG. A ferrule with a nominal length of 12mm (0.47″) is recommended. Each connector point contains a built-in test point of 1mm (.04″) diameter or 1.2 mm (.047″) diameter for troubleshooting purposes.

 

 

Hardware Safety Connection (HSC)

The Hardware Safety Connection on the Terminal Module, when connected to the Controller Module, acts as an independent shutdown signal from any terminal module to the Controller Module. Connect the Hardware Safety Connection (HSC) from each Terminal Modules’ (HSC) terminal to the Controller Module HDW SAFETY (HSC) terminal. This is a low voltage 5VDC signal.

 

INPUT SENSOR WIRING

Each Terminal Module contains up to 32 sensor inputs. The sensor wire leads connect to the pluggable terminal blocks on the Terminal Module. The input terminal numbers correspond to the HMI display channel numbers, which also have a user assigned 30-character label associated with them. The sensor inputs are numbered (IN1+, IN1-) to (IN32+, IN32-). When configuring the I/O for multiple Terminal Modules, the board number is shown first, then the channel number separated by a colon. For example, channel 15 on terminal board 1 is shown as: T1:IN15.

All unused input channels on the DE-4000 Terminal Module must be shunted to avoid unwanted noise from entering the system.

 

All unused inputs on the Terminal Module must be shunted with either switch position 1 or have a shunt jumper in place. Each input has a 4-position mechanical switch located on the Terminal Module that must be switched to the proper position for the sensor type being used.

Please note that Commencing with serial number 2300 and above (also identified as 691760 R1), a hardware change was made to the DE-4000 Terminal Module. Switch position 1 on the 4-position channel configuration switch when set to “on” shunts the input. For ease of wiring, switch position 1 can be used in place of a shunt jumper when an input is not used or is set for a normally open or 4-20mA input.

  • Unused Input – Switch Position 1 ON, 2, 3, 4 OFF
  • Normally Open Input – Switch Position 1 & 2 ON, 3 & 4 OFF
  • Normally Closed – Switch Position 2 ON, 1, 3, 4 OFF
  • 4-20 mA Input – Switch Position 1 & 3 ON, 2 & 4 OFF
  • Thermocouple Input – Switch Position 1, 2, 3, 4 OFF
  • Analog, DEG1, 2, & 3 Input – Switch Position 4 ON, 1, 2, 3 OFF

See also input sensor wiring diagram figure 11 below.

 

8.5.1 DISCRETE SENSOR INPUT WIRING

● Normally-open (N/O) sensor switches are wired with one wire to the IN+ terminal of the respective sensor number and the other to engine ground which should be the same as power minus (−). For normally-open sensor wiring, terminals (INx+) and (INx-) must also be shunted with either a shunt jumper or by turning switch 1 on.

● Normally-closed (N/C) sensor switches are wired with one wire to the (INx+) terminal and the other to the (IN-) terminal of the respective sensor number. Note that the shunt jumper must be removed.

Use a wire size between 16 AWG (max.) and 24 AWG (min.) to connect the sensor switches to the terminal strip connector. Strip the insulation back 3/8“; twist the exposed wires tightly together. Insert the exposed wire completely into the terminal strip. For wires that are fine and flexible, crimp on a ferrule. Wires running to sensor switches must be in good condition or replaced with new wires. When running wires, take care not to damage the insulation and take precautions against later damage from vibration, abrasion, or liquids in conduits. An explosion-proof conduit is not required, however, wires should be protected from damage by running them in a protective conduit or in sheaths where appropriate. In addition, it is essential that the following practices be adhered to:

A. Never run sensor wires in the same conduit with ignition wiring or other high energy wiring such as the AC line power.

B. Keep secondary wires to spark plugs and other high voltage wiring at least eight inches (200mm) away from sensor and sensor wiring.

C. Sensor switches may be connected to any passive device using contacts such as standard switch gauges, pressure or level switches.
DO NOT connect sensor leads to any voltage producing element.

D. In the case of a field conversion, where sensors have previously been used with Murphy tattletales, it is recommended that the sensors be checked frequently when the DE System is first put into use. Sensor contacts may be burned or pitted from past exposure to ignition system primary voltage. It is advisable to replace such sensors.

E. If it becomes necessary to check sensor switch to panel wiring with an ohmmeter or other checker, first DISCONNECT the plug-in terminal strips from the Terminal Module. Applying voltage to the DE-4000 System through the sensor leads may damage the device. The area should be tested as non-hazardous before such testing commences.

 

8.5.2 ANALOG SENSOR WIRING

For each analog monitored point, inputs 01–32 on each Terminal Module, select a transducer, either an Altronic pressure or temperature transducer listed above, or one that outputs a signal in the range of 0 to 5 VDC or 0 to 25 mA. Mount as described above. Use cable assembly 693008-x or similar to wire transducer to the Terminal Module. The Terminal Module provides eight each connector terminals to power the Altronic transducers. Max combined current is 400 mA. See wiring diagrams. If the 5 volt sensor supply exits the panel, it must be fused with a 0.5 ampere fuse. If 24VDC powered sensors are used, the 24 volt supply to them must be fused appropriately. Take care not to damage the insulation when installing and take precautions against later damage from vibration, abrasion, or liquids in conduits. In addition, it is essential that the following practices be adhered to:

A. Never run sensor wires in the same conduit with ignition wiring or other high energy wiring such as AC line power.

B. Keep secondary wires to spark plugs and other high voltage wiring at least eight inches (200mm) away from sensor and sensor wiring.

 

8.5.3 THERMOCOUPLES AND THERMOCOUPLE EXTENSION WIRE

Grounded or ungrounded type J or K thermocouples may be used. Use thermocouple extension wire of the same type as the thermocouple probe to connect to the terminal module. Use stranded thermocouple wire having a moisture-resistant insulation such as PVC. For higher ambient temperatures, Teflon or B-fiber insulated thermocouple wire is recommended. To ensure that an accurate signal is transmitted to the device, avoid any added junctions, splices and contact with other metals. On unused channels, leave the shunt jumper supplied with the system in place. Take care not to damage the insulation when installing and take precautions against later damage from vibration, abrasion, or liquids in conduits. In addition, it is essential that the following practices be adhered to:

A. Never run sensor wires in the same conduit with ignition wiring or other high energy wiring such as AC line power.

B. Keep secondary wires to spark plugs and other high voltage wiring at least eight inches (200mm) away from sensor and sensor wiring.

 

LUBE/NO-FLOW SENSOR

Terminal Module inputs may optionally be used for a lube/no-flow proximity cycle switch. Wire the sensor according to section 7.5.1. The sensor may be wired as either N/C or N/O with a jumper. The DIP switches on the Terminal Module must be set as an analog configuration. The lube/no-flow channels generate a fault when the time between pulses exceeds the programmed run pulse time.

 

TERMINAL MODULE OUTPUT SWITCH WIRING

Each Terminal Module provides eight discrete outputs, DO1 through DO8. These switches are fault protected, ground isolated, solid-state switches that turn on from DOx+ to DOx-. Each discrete output is rated at 60V, 2A max. These outputs can be wired as high-side or low-side switches. For wiring examples, refer to Figure 10.

 

RPM/SPEED WIRING

Typical speed signals can come from magnetic pickups or Hall effect pickups monitoring the engine flywheel or other rotating gears. Each speed input is protected from mis-wires of up to 200 volts max.

The RPMx- terminals are common to DC-. Connect the speed input to the terminals marked RPMx+ and RPMx-. Altronic magnetic pickups or Hall effect pickups are typical sources for RPM measurement.

● MAGNETIC PICKUP – Connect the two wires from the 691118 series or similar magnetic pickup to the module at terminals RPMx+ and RPMx- using cable assembly 693104 series.

● HALL EFFECT PICKUP – Connect the three wires from the 791050 series Hall effect pickup to the module at terminals RPMx+, RPMx-, and a +5 volt source using cable assembly 593050 series. Connect pickup cable wire B to a +5V supply, wire A to terminal RPMx+ (plus), and wire C to terminal RPMx- (minus). In addition, a 10,000-ohm pull-up resistor must be placed across the +5V supply to GT of the monitor. Refer to the wiring diagrams for hookup details.

 

CONTROLLER MODULE DISCRETE INPUTS:

The three discrete inputs—STOP, RESET, START—can be connected to terminals 7–10 on the back of the HMI Display Module 691766-1. This allows for a hardware connection from the STOP, RESET, and START keys on the HMI keypad to the Controller Module. Wire each connection from the Controller Module to the Display Module as follows:

● STOP (+) to STOP (terminal 7)
● RESET (+) to RESET (terminal 8)
● START (+) to START (terminal 9)
● STOP (-) to MINUS(-) (terminal 10)

The STOP, RESET, and START inputs on the Controller Module can also be connected to normally-open, momentary panel-mounted dry contact switches. Please note that these inputs are internally pulled high to 3.3VDC and are activated when switched to (-).

NOTE: One minus (-) connection only is required from the Controller Module to the Display Module; all (-) connections on the Controller Module are common.

 

 

CONTROLLER MODULE OUTPUT SWITCH WIRING

The Controller Module has four discrete outputs rated 52VDC, 1.2 amp max. The discrete outputs are typically used for on/off control of on-engine processes. Typical applications are: Fuel Valve, Ignition Shutdown, Purge, and Crank Disconnect. The discrete outputs can be configured for either shelf state (normally-open) or failsafe (normally-closed) operation and have an LED indicator associated with them. If a discrete output is configured for failsafe (energized for run), the LED will be ON in the normal run condition and OFF for a fault condition. For outputs that are configured for shelf state the LED will be OFF for normal run condition and turn ON for a fault condition. The four discrete outputs are optically isolated, bipolar solid-state switches which are isolated from power supply minus and engine ground. These outputs can be wired as high-side or low-side configurations. The output switches will be in the open (de-energized) condition when the unit is not powered.

DS01 – FUEL SHUTOFF: Typical use of Output 1 on the Controller Module is for fuel shutoff. Output 1 can be used to control a 12-24 volt fuel valve either as energized to run or pulsed to shut off.

DO NOT attempt to control a C.D.-powered fuel valve directly with any of the DSOx output switches. The C.D. ignition system exceeds the max operating voltage of the output switch. An interposing relay and a Murphy Panel Board Adapter must be used when the Fuel Valve is a C.D. ignition-type Murphy Fuel Valve.

DS02 – IGNITION SHUTDOWN: Typical use of Output 2 on the Controller Module is for Ignition Shutdown. Output 2 can be used in conjunction with the low voltage shutdown on most Altronic ignition systems. In addition DSO2 can be used to control the source power to the ignition system using a Power Management Module.

DO NOT attempt to directly ground-out (stop) a C.D. ignition system with output DSO2. The C.D. ignition system shutdown lead exceeds the max operating voltage of output switch DSO2. An interposing relay with high current contacts must be used when grounding the shutdown lead on a C.D. ignition system.

DO NOT connect directly to the ignition system common coil ground.

DS03 – CRANK DISCONNECT: Typical use of Output 3 on the Controller Module is for crank disconnect. When auto start is configured, digital output 3 is used for crank disconnect. If the voltage or current requirement of the crank disconnect solenoid is greater than 52VDC or 1.2 amp, wire DS03 to a pilot duty relay.

DSO4 – PRELUBE/POST LUBE: Typical use of Output 4 on the Controller Module is for prelube/post lube. If the voltage or current requirement of the prelube/post lube solenoid is greater than 52VDC or 1.2 amp, wire DS04 to a pilot duty relay.

 

RS-485 COMMUNICATIONS WIRING

There are two RS-485 communication ports available on the Controller Module:

RS485 1 port is used for Modbus slave data

RS485 2 is used for Modbus master data.

The DE-4000 System can communicate to other instruments, PC’s or PLC’s via the two serial RS-485 communication wires. Use a two-conductor shielded cable of fine gauge stranded wire and connect the wires to the terminals marked RS-485A, RS-485B, and shield. Make the following connections to the other communication device A to A(-) and B to B(+). If required, connect the shield wire to the master device only.

CAN COMMUNICATIONS WIRING

The CAN port on the Terminal Module is marked CANH, and CANL.

 

MODBUS ADDRESS LIST

The Default Modbus Output from the DE-4000 is listed below. 16-Bit registers are sent under Node address configured in the ‘Global’ ⇒ ‘Network’ Menu

32-Bit Registers are sent out on Node Address 200

Default 16-bit registers

 

Register Description Note
40001 Engine State 0-Ready to Run, 1-Warning, 2-PreLube, 3-Crank, 4-Ignition, 5-Fuel,
6-Crank Disconnect, 7-Warmup, 8-Running, 9-Cooldown, 10-Emergency Stop
40002 HourMeter # of Hours (Unsigned 0-65535)
40003 Hourmeter # of Minutes (0-59)
40004 Status Fault Terminal Module T1 Channel Fault = 1-32
Terminal Module T2 Channel Fault = 33-64
Terminal Module T3 Channel Fault = 65-96
Terminal Module T4 Channel Fault = 97-128
Terminal Module T5 Channel Fault = 129 – 160
Speed Channel fault = 161-170 (T1:SP1, T1:SP2, T2:SP1, T2:SP2, etc.)
Overcrank = 171, Stop = 0, Timers Active = 254, Running = 255
40005 Control Module
Output Status
BIT0 = DS1, BIT1 = DS2, BIT2 = DS3, BIT3 = DS4
40006 Fault Status 0=N/A, 1=LOW FAULT or DISCRETE FAULT, 2 = HIGH FAULT
40020 Digital Output Status
Terminal 1
40021 Digital Output Status
Terminal 2
40022 Digital Output Status
Terminal 3
40023 Digital Output Status
Terminal 4
40024 Digital Output Status
Terminal 5
40090-
40121
Terminal Module T1
Channels IN1-IN32
40122-
40153
Terminal Module T2
Channels IN1-IN32
40154-
40185
Terminal Module T3
Channels IN1-IN32
40186-
40217
Terminal Module T4
Channels IN1-IN32
40218-
40249
Terminal Module T5
Channels IN1-IN32
40250 Speed T1:SP1 Terminal 1 RPM 1
40251 Speed T1:SP2 Terminal 1 RPM 2
40252 Speed T2:SP1 Terminal 2 RPM 1
40253 Speed T2:SP2 Terminal 2 RPM 2
40254 Speed T3:SP1 Terminal 3 RPM 1
40255 Speed T3:SP2 Terminal 3 RPM 2
40256 Speed T4:SP1 Terminal 4 RPM 1
40257 Speed T4:SP2 Terminal 4 RPM 2
40258 Speed T5:SP1 Terminal 5 RPM 1
40259 Speed T5:SP2 Terminal 5 RPM 2
40260 Analog Output
T1:AO1
(0-100%)
40261 Analog Output
T1:AO2
(0-100%)
40262 Analog Output
T1:AO3
(0-100%)
40263 Analog Output
T1:AO4
(0-100%)
40264 Analog Output
T2:AO1
(0-100%)
40265 Analog Output
T2:AO2
(0-100%)
40266 Analog Output
T2:AO3
(0-100%)
40267 Analog Output
T2:AO4
(0-100%)
40268 Analog Output
T3:AO1
(0-100%)
40269 Analog Output
T3:AO2
(0-100%)
40270 Analog Output
T3:AO3
(0-100%)
40271 Analog Output
T3:AO4
(0-100%)
40272 Analog Output
T4:AO1
(0-100%)
40273 Analog Output
T4:AO2
(0-100%)
40274 Analog Output
T4:AO3
(0-100%)
40275 Analog Output
T4:AO4
(0-100%)
40276 Analog Output
T5:AO1
(0-100%)
40277 Analog Output
T5:AO2
(0-100%)
40278 Analog Output
T5:AO3
(0-100%)
40279 Analog Output
T5:AO4
(0-100%)

 

Default 32-bit registers

All 32-bit Registers are Float 32 and are available under node 200

High Bit
Register
Low Bit
Register
Note High Bit
Register
Low Bit
Register
Note
40001 40002 T1:IN1 40065 40066 T2:IN1
40003 40004 T1:IN2 40067 40068 T2:IN2
40005 40006 T1:IN3 40069 40070 T2:IN3
40007 40008 T1:IN4 40071 40072 T2:IN4
40009 40010 T1:IN5 40073 40074 T2:IN5
40011 40012 T1:IN6 40075 40076 T2:IN6
40013 40014 T1:IN7 40077 40078 T2:IN7
40015 40016 T1:IN8 40079 40080 T2:IN8
40017 40018 T1:IN9 40081 40082 T2:IN9
40019 40020 T1:IN10 40083 40084 T2:IN10
40021 40022 T1:IN11 40085 40086 T2:IN11
40023 40024 T1:IN12 40087 40088 T2:IN12
40025 40026 T1:IN13 40089 40090 T2:IN13
40027 40028 T1:IN14 40091 40092 T2:IN14
40029 40030 T1:IN15 40093 40094 T2:IN15
40031 40032 T1:IN16 40095 40096 T2:IN16
40033 40034 T1:IN17 40097 40098 T2:IN17
40035 40036 T1:IN18 40099 40100 T2:IN18
40037 40038 T1:IN19 40101 40102 T2:IN19
40039 40040 T1:IN20 40103 40104 T2:IN20
40041 40042 T1:IN21 40105 40106 T2:IN21
40043 40044 T1:IN22 40107 40108 T2:IN22
40045 40046 T1:IN23 40109 40110 T2:IN23
40047 40048 T1:IN24 40111 40112 T2:IN24
40049 40050 T1:IN25 40113 40114 T2:IN25
40051 40052 T1:IN26 40115 40116 T2:IN26
40053 40054 T1:IN27 40117 40118 T2:IN27
40055 40056 T1:IN28 40119 40120 T2:IN28
40057 40058 T1:IN29 40121 40122 T2:IN29
40059 40060 T1:IN30 40123 40124 T2:IN30
40061 40062 T1:IN31 40125 40126 T2:IN31
40063 40064 T1:IN32 40127 40128 T2:IN32
High Bit
Register
Low Bit
Register
Note High Bit
Register
Low Bit
Register
Note
40129 40130 T3:IN1 40193 40194 T4:IN1
40131 40132 T3:IN2 40195 40196 T4:IN2
40133 40134 T3:IN3 40197 40198 T4:IN3
40135 40136 T3:IN4 40199 40200 T4:IN4
40137 40138 T3:IN5 40201 40202 T4:IN5
40139 40140 T3:IN6 40203 40204 T4:IN6
40141 40142 T3:IN7 40205 40206 T4:IN7
40143 40144 T3:IN8 40207 40208 T4:IN8
40145 40146 T3:IN9 40209 40210 T4:IN9
40147 40148 T3:IN10 40211 40212 T4:IN10
40149 40150 T3:IN11 40213 40214 T4:IN11
40151 40152 T3:IN12 40215 40216 T4:IN12
40153 40154 T3:IN13 40217 40218 T4:IN13
40155 40156 T3:IN14 40219 40220 T4:IN14
40157 40158 T3:IN15 40221 40222 T4:IN15
40159 40160 T3:IN16 40223 40224 T4:IN16
40161 40162 T3:IN17 40225 40226 T4:IN17
40163 40164 T3:IN18 40227 40228 T4:IN18
40165 40166 T3:IN19 40229 40230 T4:IN19
40167 40168 T3:IN20 40231 40232 T4:IN20
40169 40170 T3:IN21 40233 40234 T4:IN21
40171 40172 T3:IN22 40235 40236 T4:IN22
40173 40174 T3:IN23 40237 40238 T4:IN23
40175 40176 T3:IN24 40239 40240 T4:IN24
40177 40178 T3:IN25 40241 40242 T4:IN25
40179 40180 T3:IN26 40243 40244 T4:IN26
40181 40182 T3:IN27 40245 40246 T4:IN27
40183 40184 T3:IN28 40247 40248 T4:IN28
40185 40186 T3:IN29 40249 40250 T4:IN29
40187 40188 T3:IN30 40251 40252 T4:IN30
40189 40190 T3:IN31 40253 40254 T4:IN31
40191 40192 T3:IN32 40255 40256 T4:IN32
High Bit
Register
Low Bit
Register
Note
40257 40258 T5:IN1
40259 40260 T5:IN2
40261 40262 T5:IN3
40263 40264 T5:IN4
40265 40266 T5:IN5
40267 40268 T5:IN6
40269 40270 T5:IN7
40271 40272 T5:IN8
40273 40274 T5:IN9
40275 40276 T5:IN10
40277 40278 T5:IN11
40279 40280 T5:IN12
40281 40282 T5:IN13
40283 40284 T5:IN14
40285 40286 T5:IN15
40287 40288 T5:IN16
40289 40290 T5:IN17
40291 40292 T5:IN18
40293 40294 T5:IN19
40295 40296 T5:IN20
40297 40298 T5:IN21
40299 40300 T5:IN22
40301 40302 T5:IN23
40303 40304 T5:IN24
40305 40306 T5:IN25
40307 40308 T5:IN26
40309 40310 T5:IN27
40311 40312 T5:IN28
40313 40314 T5:IN29
40315 40316 T5:IN30
40317 40318 T5:IN31
40319 40320 T5:IN32
PID1 PID2
Register Description Note Register Description Note
40400:
40401
Enable 0=Disable
1=Enable
40430:
40431
Enable 0=Disable
1=Enable
40402:
40403
P-Factor 40432:
40433
P-Factor
40404:
40405
I-Factor 40434:
40435
I-Factor
40406:
40407
D-Factor 40436:
40437
D-Factor
40408:
40409
Max Limit 40438:
40439
Max Limit
40410:
40411
Min Limit 40440:
40441
Min Limit
40412:
40413
Input
Terminal
1-5 40442:
40443
Input
Terminal
1-5
40414:
40415
Input
Channel
1-32 40444:
40445
Input
Channel
1-32
40416:
40417
Output
Terminal
1-5 40446:
40447
Output
Terminal
1-5
40418:
40419
Output
Channel
1-32 40448:
40449
Output
Channel
1-32
40420:
40421
Deadband 40450:
40451
Deadband
40422:
40423
Setpoint 40452:
40453
Setpoint
PID3 PID4
Register Description Note Register Description Note
40460:
40461
Enable 0=Disable
1=Enable
40490:
40491
Enable 0=Disable
1=Enable
40462:
40463
P-Factor 40492:
40493
P-Factor
40464:
40465
I-Factor 40494:
40495
I-Factor
40466:
40467
D-Factor 40496:
40497
D-Factor
40468:
40469
Max Limit 40498:
40499
Max Limit
40470:
40471
Min Limit 40500:
40501
Min Limit
40472:
40473
Input
Terminal
1-5 40502:
40503
Input
Terminal
1-5
40474:
40475
Input
Channel
1-32 40504:
40505
Input
Channel
1-32
40476:
40477
Output
Terminal
1-5 40506:
40507
Output
Terminal
1-5
40478:
40479
Output
Channel
1-32 40508:
40509
Output
Channel
1-32
40480:
40481
Deadband 40510:
40511
Deadband
40482:
40483
Setpoint 40512:
40513
Setpoint
PID5 PID6
Register Description Note Register Description Note
40520:
40521
Enable 0=Disable
1=Enable
40550:
40551
Enable 0=Disable
1=Enable
40522:
40523
P-Factor 40552:
40553
P-Factor
40524:
40525
I-Factor 40554:
40555
I-Factor
40526:
40527
D-Factor 40556:
40557
D-Factor
40528:
40529
Max Limit 40558:
40559
Max Limit
40530:
40531
Min Limit 40560:
40561
Min Limit
40532:
40533
Input
Terminal
1-5 40562:
40563
Input
Terminal
1-5
40534:
40535
Input
Channel
1-32 40564:
40565
Input
Channel
1-32
40536:
40537
Output
Terminal
1-5 40566:
40567
Output
Terminal
1-5
40538:
40539
Output
Channel
1-32 40568:
40569
Output
Channel
1-32
40540:
40541
Deadband 40570:
40571
Deadband
40542:
40543
Setpoint 40572:
40573
Setpoint
PID7 PID8
Register Description Note Register Description Note
40580:
40581
Enable 0=Disable
1=Enable
40610:
40611
Enable 0=Disable
1=Enable
40582:
40583
P-Factor 40612:
40613
P-Factor
40584:
40585
I-Factor 40614:
40615
I-Factor
40586:
40587
D-Factor 40616:
40617
D-Factor
40588:
40589
Max Limit 40618:
40619
Max Limit
40590:
40591
Min Limit 40620:
40621
Min Limit
40592:
40593
Input
Terminal
1-5 40622:
40623
Input
Terminal
1-5
40594:
40595
Input
Channel
1-32 40624:
40625
Input
Channel
1-32
40596:
40597
Output
Terminal
1-5 40626:
40627
Output
Terminal
1-5
40598:
40599
Output
Channel
1-32 40628:
40629
Output
Channel
1-32
40600:
40601
Deadband 40630:
40631
Deadband
40602:
40603
Setpoint 40632:
40633
Setpoint
PID9 PID10
Register Description Note Register Description Note
40640:
40641
Enable 0=Disable
1=Enable
40670:
40671
Enable 0=Disable
1=Enable
40642:
40643
P-Factor 40672:
40673
P-Factor
40644:
40645
I-Factor 40674:
40675
I-Factor
40646:
40647
D-Factor 40676:
40677
D-Factor
40648:
40649
Max Limit 40678:
40679
Max Limit
40650:
40651
Min Limit 40680:
40681
Min Limit
40652:
40653
Input
Terminal
1-5 40682:
40683
Input
Terminal
1-5
40654:
40655
Input
Channel
1-32 40684:
40685
Input
Channel
1-32
40656:
40657
Output
Terminal
1-5 40686:
40687
Output
Terminal
1-5
40658:
40659
Output
Channel
1-32 40688:
40689
Output
Channel
1-32
40660:
40661
Deadband 40690:
40691
Deadband
40662:
40663
Setpoint 40692:
40693
Setpoint
Key Command Registers
Register Note
40700 Main Key Command Register
Write 1 for Star
Write 2 for Reset
Write 3 for Stop
Write 4 for Cancel Timers
40701 Start Key Command
(Write any value to start)
40702 Reset Key Command
(Write any value to reset)
40703 Stop Key Command
(Write any value to stop)
40704 Cancel Timers Key Command
(Write any value to Cancel Timers)
Key Commands are 16-Bit Registers
Global/Control
Register Description Note
40800:
40801
Input #1
Enable
0=Disable
1=Enable
40802:
40803
Input #2
Enable
0=Disable
1=Enable
40804:
40805
Input #1
0% Output
40806:
40807
Input #1
100% Output
40808:
40809
Input #2
0% Output
40810:
40811
Input #2
100% Output
40812:
40813
Input #1
Linear/PID
0=Linear
1=PID
40814:
40815
Input #2
Linear/PID
0=Linear
1=PID
40816:
40817
Input #1
Terminal
1-5
40818:
40819
Input #1
Channel
1-32
40820:
40821
Input #2
Terminal
1-5
40822:
40823
Input #2
Channel
1-32
40824:
40825
Output #1
Terminal
1-5
40826:
40827
Output #1
Channel
1-4
40828:
40829
Output #2
Terminal
1-5
40830:
40831
Output #2
Channel
1-4
40832:
40833
Output #1
Low
40834:
40835
Output #1
High
40836:
40837
Output #2
Low
40838:
40839
Output #2
High
40840:
40841
Output #1
Ramp Rate
40842:
40843
Output #2
Ramp Rate
40844:
40845
Output #1
Reverse Action
0=Normal
1=Reverse
40846:
40847
Output #2
Reverse Action
0=Normal
1=Reverse
40848:
40849
Input #1
P-Factor
40850:
40851
Input #1
I-Factor
40852:
40853
Input #1
D-Factor
40854:
40855
Input #2
P-Factor
40856:
40857
Input #2
I-Factor
40858:
40859
Input #2
D-Factor
40860:
40861
Auto/Manual Toggle
Input Terminal
1-5
40862:
40863
Auto/Manual Toggle
Input Channel
1-32
40864:
40865
Speed Control
Mode
0=Manual
1=Auto
40866:
40867
Manual
Speed
value in
RPM

Registers 41001 – 41998 are the Register Mirror Test Area(Any value written to these registers will be able to be read starting at register 30001. For example you can write a 32 bit value at 41001,41002 and read it at 30001, 30002)

Starting at register 42000:42001 The Safety Setpoint for each channel is store. First High then Low.
Example: 42000:42001 is Terminal 1 Input 1 High Safety Setpoint and 42002:42003 is Terminal 1 Input 1 Low Safety Setpoint.

There is 100 register spacing between channels so Terminal 1 Input 2 High and Low Safety Setpoints are registers 42100:42101 and 42102:42103

This continues for 32 channels per terminal board with 5 Terminal Boards Max

HAZARDOUS AREA OPERATION

General

The DE-4000 Series Configurable Safety Shutdown and Control System is CSA (C/US) – certified for Class I, Division 2, Groups C and D areas or non-hazardous locations.

● The HMI Display Module is CSA certified (C/US) with an ambient temperature range of -30°C to 80°C (-22°F to 176°F) temperature code T4

● The Controller Module is CSA certified (C/US) with an ambient temperature range of -40°C to 85°C (-40°F to 185°F) temperature code T4

● The Terminal Module is CSA certified (C/US) with an ambient temperature range of -40°C to 85°C (-40°F to 185°F) temperature code T3C

The DE-4000 System must be installed in a suitable enclosure.

The following requirements must also be met (refer to NFPA standard no. 493):

● The low voltage sensor switch wires within the panel enclosure must be kept at least two (2) inches away from other wiring. Run the sensor switch wires leaving the panel in a separate conduit from all other wiring and keep them separate throughout the installation.

● Wiring to the sensors must have a grade of insulation capable of withstanding an AC voltage of 500 volts RMS.

● Sensor wires must be run in separate conduits and junction boxes from high voltage wires such as ignition, fuel valve, and other high voltage wiring.

WARNING: Substitution of components may impair intrinsic safety and/or suitability for Class I, Div. 2, Groups C and D. Do not disconnect equipment in Div. 2 environment unless power is switched off or the area is known to be non-hazardous.

 

 

Power

The power for the DE-4000 System must be from a Class 2 power source with transient protection or from a 24-volt battery system.

The DE-4000 System must be installed in accordance with the requirements of the National Electrical Code (US) and the Canadian Electrical Code (Canada)

 

WARNINGS

● WARNING – EXPLOSION HAZARD – Substitution of components may impair intrinsic safety and/or suitability for Class 1, Div. 2, Groups C and D.

● AVERTISSEMENT – RISQUE D’EXPLOSION – La substitution de composants eutrendre ce materiel inacceptable pour les emplacements de Classe I, Division 2.

● WARNING – EXPLOSION HAZARD – Do not disconnect equipment in Div. 2 environment unless power is switched off or the area is known to be nonhazardous.

● AVERTISSEMENT – RISQUE D’EXPLOSION – Avant de deconnecter l’equipement, couper le courant ou s’assurer que l’emplacement est designe non.

● Warning – EXPLOSION HAZARD – Do not use USB connectors in hazardous area.

● AVERTISSEMENT – RISQUE D’EXPLOSION – Ne pas utiliser les connecteurs USB en zone dangereuse.

 

IP54

When the DE-4000 System is installed in hazardous area, it shall be installed in a suitable enclosure which provides an ingress protection minimum level of IP54 (splash protected).

 

Inputs

The inputs are rated non-incendive:

● Terminal Module – when the inputs are configured as:

  • “Discrete” or “Digital” inputs must be connected to passive switches only.
  • When configured as thermocouple, inputs must be connected to thermocouples only.
  • When connected as an analog input, inputs must not exceed 5VDC.
  • When connected as 4-20mA, inputs must not exceed 24mA.

● RPM inputs – when connected to Altronic 691118-x magnetic pickup or Altronic 791050-x Hall Effect pickup. Both pickups are CSA approved as non-incendive outputs.
● Controller Module Discrete Inputs – when connected to dry contacts.

 

WiFi Antenna

Coaxial cable leaving the system enclosure shall be routed in conduit or be protected by another approved Division 2 wiring method. The antenna itself shall be located in a non-hazardous area, or shall not have exposed bare metal elements.

 

CONNECTING VIA ETHERNET TO CONFIGURE THE DE-4000

General

Each DE-4000 System requires configuration prior to use. The DE-4000 is a web-enabled smart device. Configuration of the DE-4000 is through the web interface. Unlike previous DE products, there is no stand-alone “Terminal Program”. A standard laptop computer with a hard-wired ethernet connection and a web browser is required for configuration. A CAT5 or CAT6 cable, terminated with a standard RJ45 connector on both ends, is required. Ethernet Cable, CAT5 1.0m (39”) (693221-2) is a suitable cable available from Altronic.

A network connection is required to connect the laptop PC to the DE-4000. This can be accomplished in one of two ways, a temporary change to the TCP/ IP configuration of the existing network adapter on your laptop PC, or to create a separate private network using a second network adapter to build a private network. The necessary steps to accomplish this vary with your operating system. Temporarily changing the TCP/IP configuration of the existing network adapter is outlined below for Microsoft® Windows-based computers. The laptop PC must have at least one Network Interface Card (NIC) installed.

● IP Address 98.102.65.174 is the default IP address for the DE-4000 System.
● The IP address of your laptop PC network interface must be set to an address of 98.102.65.x, where x is any integer from 1 to 254, excluding the range of 160-174.
● The IP address on your laptop PC must be set to static. The PC is typically configured to obtain an IP address dynamically; if so, you will usually have no control over its address and will have to set it to static.
Follow the procedure below for Microsoft® Windows 10 operating system:
1. From the Microsoft® Windows 10 desktop, click on the Windows Button in the lower left-hand corner and then click on Control Panel.

2. Click on Network and Sharing Center.

3. Click on Change Adapter Settings.

4. Right Click on Ethernet and select Properties

5. Click on the Internet Protocol Version 4 (TCP/IPv4) item and click on the Properties button.

6. Click on the Use the following IP address: option.

7. Change the IP address to 98.102.65.xxx (for example 98.102.65.115).

8. Change the Subnet Mask to 255.255.255.0.

9. Click OK.

10. Click OK on the Ethernet Properties screen.

11. Exit out of the Network Connections Status screen.

For a visual step-by-step process, please refer to the document How to change a computers IP address for hardwiring into the DE-4000 on the Altronic website www.altronic-llc.com under Controllers.

● A web browser on the laptop PC is used to communicate to the DE-4000 System. Preferred browsers are Google® Chrome and Firefox.

● Open the web browser and type in the IP address (98.102.65.174). The DE-4000 configuration page will be loaded.

 List of Figures

 

System Diagram and General Hookup

Power Distribution and Hardware Safety Diagram

System Configuration Connection, Controller Module

HMI Display Module, Dimensions and Specifications

  • LCD Description: 8” 1024 x 768 XGA Anti-Glare/Anti Reflective 4:3 ratio with PCAP touch and LED Backlight
  • Dimensions: Front panel 9” x 9”
  • Input Power – 10-32VDC, 2A max
  • Temp Range: -30°C to 80°C
  • Power Connection: 3-pin pluggable Phoenix
  • Pluggable Connection points:
    • RS-485 A(-), B(+), GND
    • CAN H, CAN L,CAN GND
    • STOP, RESET, TEST, GND (internally connected to front keypad switches)
  • Front Panel side of LCD is IP67 sealed
  • Outdoor and Indoor use
  • Backlight intensity: 1000nit max,
  • Backlight dimming: Auto or Manual
  • Communications:
    • 1 each 10/100 Ethernet port, RJ45 used to connect to the controller module
    • 1 each CAN port
    • 1 each RS485 port
    • 2 each USB Ports
    • 1 each USB OTG Port
  • Keypad: 5 keys
    • Stop
    • Reset
    • Test
    • F1
    • F2

 

Controller Module, Dimensions

 

Controller Module, Specifications

  • Input Power – 10-32VDC, 2A max
  • 5 amp automotive type blade fuse
  • Operating Temperature Range – -40°C to 85°C
  • Hazardous Area Classification – CSA, UL Class I, Div 2, Groups C and D
  • Hardware Safety Connection (HSC) – Can be connected to each terminal module as an independent shutdown signal from any of the terminal modules. Triggers Discrete Output #1, independent of the Controller Module’s microcontroller.
  • Discrete Inputs – Stop, Reset, Test; Emulates hard contacts stop, reset, test on the legacy Annunciators, can be connected to the LCD Display Module keypad, connect + to – to activate.
    • LED Indicators, on when active
      • Stop – Red
      • Reset – Blue
      • Test – Yellow
  • Discrete Outputs – 4 each Isolated Discrete Outputs, Emulates the four outputs on the DE-2000/3000 Power Supply. Open with absence of power, low or high-side connection solid state switches rated 52VDC, 1.2A max. LED Indicator for each output switch, on when active, blue color.
  • Communications –
    • 5 each 10/100 Ethernet port, RJ45 used to connect to up to 5 Terminal Modules
    • 1 each 10/100 Ethernet port, RJ45 used to connect to the LCD Module
    • 1 each 10/100 Ethernet port, RJ45 used to connect to PC’s, PLCs, SCADA Systems, Telematics systems and an outside network
    • LED indicators on each of the RJ45 connectors, indicate activity (green) and Link (Yellow)
    • 1 each CAN port
    • 2 each RS485 ports, one Master, one Slave.
    • LED indicators on each of the RS485 ports, RX, TX
  • USB – 2.0B Type A and B
    • Type A connector, host or hub
    • Type B connector, device
  • Real time clock – Lithium Coin cell battery, est 10 year life.
  • WiFi – Single stream 2.4GHz band, IEEE 802.11 b/g/n, temp range -40°C to 85°C
  • WiFi Antenna – 6.35 mm, 50 ohm, threaded SMA connector on board allows for remote antenna mounting using SMA type RF connector.
    • Dipole antenna type having a maximum gain of 2.14 dBi
  • LED, Power and Status
    • Power – Green – Input voltage OK or red – out of range
    • Status – Amber – various blink patterns
    • Power – Blue
    • Status – Amber
  • LED Indicators for Run, Timers Active, Alarm, Stop
    • Run – Green
    • Timers Active – Yellow
    • Alarm – Orange
    • Stop – Red
  • On-Board uSD card socket, used for data logging memory and device backup and recovery

Terminal Module, Dimensions

Terminal Module, Specifications

  • Input Power – 10-32VDC, 2A max
  • 5 amp automotive type blade fuse
  • Operating Temperature Range – -40°C to 85°C
  • Hazardous Area Classification – CSA, UL Class I, Div 2, Groups C and D
  • Configurable Inputs –32 each, protected 0-5V_ 0-20mA_TC, J,K_NO/NC Discrete Inputs configured by a 4-position slide switch
    • Over voltage protection
    • Channel to channel isolation protection from each channel
  • Input Scan rate – 10ms per channel (dual track) 160ms one complete cycle.
  • Speed Inputs – 2 each, 5 volts – 100 volts, 0 – 10KHz
  • Analog Outputs – 4 each, 0-24mA
  • Discrete Outputs – 8 each, 40Vdc, 2A max each solid state smart switches with diagnostics (over current, over temp) can be wired for high or low side operation. Dual LED indicators one for each output; green indicates the output is energized, red shows a fault condition.
  • Hardware Safety Connection – Can be connected to the Controller Module as an independent shutdown signal from any of the terminal modules. Triggers Discrete Output #1, on the Controller Module independent of the Controller Module’s microcontroller.
  • Communications –
    • 1 each 10/100 Ethernet port, RJ45 used to connect to the controller module
    • 1 each CAN port
    • 1 each RS485 port
  • Auxiliary Supply (5V) – 8 each 5V, 400 mA total for supply to 5V transducers, protected from shorts, reverse connection
  • LED Indicators:
    • Power – Green – power good, Red – Supply voltage out of tolerance
    • RS485 – RX / TX
  • 10-Position Rotary Switch – Selects board ID Number.
    • Switch position 1 = board 1
    • Switch position 2 = board 2
    • Switch position 2 = board 3
    • Switch position 2 = board 4
    • Switch position 2 = board 5

Wiring Diagram – Controller, Power and Outputs

NOTES:
1. DISCRETE OUTPUT SWITCHES CAN BE CONNECTED AS EITHER LO-SIDE OR HIGH-SIDE NEITHER THE (+) OR (-) IS TIED INTERNALLY.
2. DISCRETE OUTPUTS:

  • OUTPUT 1 TYPICAL USE: 24 VDC POWERED FUEL VALVE.
  • OUTPUT 2 TYPICAL USE: LOW VOLTAGE IGNITION SHUTDOWN.
  • OUTPUT 3 TYPICAL USE: CRANK DISCONNECT.
  • OUTPUT 4 TYPICAL USE: PRELUBE / POSTLUBE.

Wiring Diagram – Controller, Inputs and Communications

NOTES:
1. DRY MOMENTARY PUSH BUTTON SWITCHES ARE REQUIRED FOR STOP, RESET, AND TEST. THEY ARE PULLED HIGH INTERNALLY TO 3.3 V AND GET GROUNDED TO (-) TO ACTIVATE THE CONDITION.

Wiring Diagram – Terminal, Sensor and Transducers Inputs

NOTES:

  1. USING THE CONFIGURATION SWITCH, EACH CHANNEL MUST BE CONFIGURED FOR NO, NC, ANALOG INPUT, THERMOCOUPLE OR 4-20mA.
  2. ALL UNUSED INPUTS MUST BE SHUNTED WITH EITHER SWITCH POSITION 1 OR HAVE A SHUNT JUMPER IN PLACE.
  3. N/O SENSOR SWITCH AND 4-20mA MUST HAVE SWITCH POSITION 1 ON OR JUMPER IN PLACE BETWEEN (+) AND (-) OF TERMINAL BLOCK. POWER SUPPLY MINUS AND SENSOR GROUND MUST BOTH BE COMMON.
  4. N/C SENSOR SWITCH, REMOVE JUMPER AND PLACE SWITCH WIRES, ONE IN (+) OTHER IN (-).
  5. THE +5VDC INTERNAL SUPPLY OUTPUT IS LIMITED TO 500 mA MAXIMUM. IF THIS SUPPLY EXITS THE PANEL, IT MUST BE FUSED WITH A 0.5 AMPERE FUSE. ALL +5VDC TERMINALS ARE ELECTRICALLY CONNECTED TOGETHER. EIGHT TERMINALS ARE PROVIDED FOR WIRING CONVENIENCE ONLY.
  6. 24 VOLT POWER TO 4-20mA TRANSMITTERS MUST HAVE A COMMON GROUND TO POWER SUPPLY.

Wiring Diagram – Terminal, Digital Outputs

NOTES:

  1. DISCRETE OUTPUT SWITCHES CAN BE CONNECTED AS EITHER LO-SIDE OR HIGH-SIDE NEITHER THE (+) OR (-) IS TIED INTERNALLY.
  2. SOLENOID VALVE: 4 WAY SOLENOID CLOSED-CENTER TYPE. BOTH PORTS BLOCKED IN CENTER POSITION WITH SOLENOIDS DE-ENERGIZED.
  3. DIGITAL OUTPUT 1 ENERGIZED TO LOAD, DIGITAL OUTPUT 2 ENERGIZED TO UNLOAD.
  4. THIS DIAGRAM SHOWS TYPICAL CONNECTIONS. FOLLOW MANUFACTURERS RECOMMENDATIONS FOR COMPLETE SYSTEM COMPONENTS AND HOOK-UP.
  5. USE PILOT DUTY RELAYS CONNECTED TO DIGITAL OUTPUTS TO CONTROL.
    • OIL OR WATER COOLERS
    • OIL TEMPERATURE CONTROL VALVE
    • OIL HEATERS
    • PRELUBE PUMPS
    • AND OTHER MEDIUM TO HIGH CURRENT AUXILIARY EQUIPMENT

Wiring Diagram – Terminal Current Loop Outputs

NOTES:

  1. CURRENT LOOP OUTPUT 1 IS TYPICALLY USED TO CONTROL CAPACITY CONTROL. CURRENT LOOP OUTPUT 2 IS TYPICALLY USED AS A GOVERNOR SPEED SETPOINT FOR SPEED CONTROL.
  2. FOLLOW MANUFACTURERS RECOMMENDATIONS FOR MOUNTING AND MECHANICAL HOOK-UP OF CURRENT LOOP CONVERTERS.
  3. CONNECT HARDWARE SAFETY CONNECTION (HSC) FROM EACH OF THE TERMINAL MODULES TO THE HSC CONNECTION ON CONTROLLER MODULE.

Wiring Diagram – Terminal, RPM Inputs

NOTE: EITHER RPM INPUT CAN ACCEPT A MAGNETIC OR HALL EFFECT PICKUP.