- 4 and 8 point models
- Individual setpoint for each channel
- Microprocessor-based
- Universal features:
- Power from C.D. ignition or 12-48 Vdc
- Selectable type J or K thermocouple
- Selectable degrees C or F readout
- Solid-state N.O. limit switches.
- Temperature limits set from front using the display readout
- Rugged, anodized aluminum case
- Engine cylinder exhaust temperatures
- Engine water and oil temperatures
- Compressor process gad temperatures
- Turbocharger inlet/outlet temperatures
- Catalytic converter inlet/outlet temperatures
- Critical temperatures on any type of machinery
- Power Requirement
- C.D. ignition (110V min.) or 12-48 Vdc
- Hazardous Area Classification
- Class I, Div. 2, Group D
See “To Order” for Class I, Div. 1, Group D
- Class I, Div. 2, Group D
- Instrument Display
- 5-digit LCD, 0.4” height
- Display Readout
- Degrees C. or F. (user selectable)
- Instrument Range
- Readout
- 32°F. to 1500°F. / 0°C. to 800°C.
- Setpoint
-
- 160°F. to 1400°F. / 0°C. to 760°C.
-
- Readout
- Instrument Accuracy
- ±1% of reading
- ±3 degrees
- Display Update Rate
- 3 times per second
- Setpoint Switch Rating
- DPYH-4394U
- 400 Vdc, 0.15 amp continuous
- DPYH-4398U
- 50 Vdc, 0.1 amp continuous
- DPYH-4394U
- Ambient Temperature Rating
- -40°F. to +175°F.
- -40°C. to +80°C.
- Thermocouple Type
- Type J or K (user selectable)
- Cold Junction Compensation
- Automatic