The MOD+/MTB product combination allows the MTB board data to easily interface to popular PLCs, SCADA systems and computers over Ethernet.
The MOD+/MTB has two user-selectable communication protocols available, EtherNet/IP and Modbus/TCP. The MOD+/MTB combination allows integrators to read multi-channel analog and digital data using the MTB Board and communicate that data to Allen Bradley ControlLogix and CompactLogix, and other PLC’s via the MOD+ Module. This document gives an overview of the MOD+ and the MTB. It also lists the Ethernet/IP Object Model Data for the MOD+/MTB combination. For detailed Installation, Operation, and application information for each product, please refer to the following documents: Ethernet Interface Module – MOD+ IOM, Installation & Operating Manual Modbus Terminal Board – MTB IOI, Installation & Operating Instructions.
- Ethernet Interface Module (MOD+)
- The Altronic MOD+ Ethernet Interface Module is a protocol converter designed to convert Modbus RTU register data from the connected product into either Ethernet/IP or Modbus/ TCP formats. The MOD+ has one RS485 Modbus Master port to allow it to be connected to one Modbus RTU slave device.
- It has an integral standard RJ45 Ethernet communications port used to output Ethernet/ IP or Modbus TCP. Ethernet/IP is meant to talk to Allen Bradley ControlLogix and CompactLogix PLC’s. Modbus/TCP is meant to communicate to PLC’s and PC’s.
- Modbus Terminal Board (MTB)
- The Modbus Terminal Board is an RS-485, MODBUS RTU slave board capable of reading 33 channels. The first 30 channels can be any combination of digital inputs (N/O or N/C), thermocouples (J or K), pressure inputs, 4-20mA inputs, or read any sensor within the range of 0-5VDC. Channels 31 and 32 can only be
used for digital inputs (N/O or N/C). There is also a pickup input. - Additionally, there are 8 digital outputs which are capable of sinking 60V at 500mA.
- Each can drive a relay, horn or other related device. There are also two 4-20mA outputs. All of the outputs are directly controlled by Modbus commands. The RS-485 slave communications configuration is 38.4k baud, 8, N, 1.
- Personality Profile: In Ethernet/IP mode the MO
Product Information
Installation / Operating
- MTB 30 Channels Installation and Operating Manual
- MTB 16 Channels Installation and Operating Manual
- MOD+ Installation and Operating Manual
Programming