The PLC+ product line was developed by Altronic to allow easy integration of engine/compressor/generator function specific I/O through Ethernet to industry standard PLCs. The PLC+ Modules are designed to seamlessly deliver efficient, hazardous area approved, cost effective I/O functions that are not normally available by off-the-shelf PLC hardware. The PLC+ modules were designed with Rockwell Automation Control Logix and Compact Logix in mind. EtherNet/IP, implemented in the PLC+ Monitors, along with ModbusTCP allow seamless communication over Ethernet to Rockwell Automation PLCs as well as a wide range of other industrial PLCs. The PLC+ Monitors are based upon taking a time tested Altronic designed and tested specialty I/O function such as Analog and digital I/O, vibration, detonation, speed, and others and marrying it to a communications board packaged in a rugged cost effective shock and dust-resistant package. The VSM+ Vibration Sensing Monitor is a module in the PLC+ product line. It uses the patented vibration monitoring technique of the VSM-800 and adds an integrated Ethernet port. It is designed to protect industrial engines, compressors, and associated equipment from damage caused by excessive vibration. It accepts up to 8 industry-standard, low-cost, broadband, piezoelectric vibration sensors that are used to transform mechanical vibrations into electrical signals which are then evaluated by the VSM+. Each input channel operates independently of the other. It is designed for use as a component of a PLC+ Control Panel, or as a stand-alone product. PLC+ panels use one or more such devices for engine control and monitoring. The Ethernet port allows the monitored values to be communicated to a PC, PLC, or other communications device using either Modbus/TCP or EtherNet/IP protocol. These values can be displayed on an HMI display and compared to user adjustable setpoint levels for alarm and shutdown.
- Protects equipment from damage due to excessive vibration n Can monitor up to 8 points of interest on a natural gas or diesel engine, compressor (air or gas), pump, or other process
- Specifically designed to interface with PLC+ panels and HMIs
- Integral Ethernet port for communications to a PLC/PC or other communication device
- User-selectable communication protocols: EtherNet/IP™ or Modbus/TCP
- Eliminates vibration switches that are vulnerable to misapplication, setpoint tampering, and physical damage
- Uses low-cost automotive, piezoelectric vibration sensors as sensor inputs
- Provides two vibration-level setpoints (alarm and shutdown) which are associated with internal output switches
- Built-in bad sensor diagnostic
- Pluggable connectors with convenient push-in spring-cage connections
- On board diagnostic LEDs
- “Wink-Mode” for multiple PLC device identification
- Din-Rail mounted
- Manual and automatic disabling modes which temporarily disable the VSM+ output switches during equipment startups to prevent nuisance alarms and shutdowns
- CSA Certified Class I, Division 2, Group C and D